1 | AS110V12K3SD + BAT | Simplified System with two DC output voltage

  • 400Vac / 50Hz / CFP > 0.99
  • 12kVA Isolation Transformer (Optional)
  • Output 110Vdc / 80A (6xAE1500)
  • Output 48Vdc / 66A (3xSD1000H)
  • Flexible modular configuration (N+1)
  • Hot Plugging Switching Rectifier (FR)
  • Hot plugging DC/DC (SD) converter
  • Diode reduction system (optional)
  • Hot plugging ground fault detection unit (DPT)
  • Independent 110Vdc Maximum Voltage Sensor (SMT)
  • Tele-signaling unit (CLP) with potential-free contacts
  • Digital or analog voltmeters and ammeters for measuring battery voltage/current, and output voltage/current of the two output
  • 9 VRLA battery packs with capacity up to 200Ah, fixed in 3 shelves with liquid drain to retention basin (other solutions available)
  • Output voltage variation according to the temperature
  • Manual Battery Capacity Testing
  • Flexibility for various types of batteries
  • Warranty of 2 to 5 Years
  • EU Declaration of Conformity

2 | AS110V6K3SD + BAT | Simplified System with two DC output voltage

  • Input: 400Vac / 50Hz / CFP > 0.99
  • 6kVA Isolation Transformer (optional)
  • Output 110Vcc / 40A (3xAE1500)
  • Output 48Vcc / 66A (3xSD1000H) or Output 24Vcc / 120A (3xSD1000H24) or Output at 12Vcc / 120A (3xSD500H)
  • Flexible modular configuration (N+1)
  • Hot Plugging Switching Rectifier (FR)
  • Hot plugging DC/DC (SD) converter
  • Diode reduction system (optional)
  • Hot plugging ground fault detection unit (DPT)
  • Independent 110Vdc Maximum Voltage Sensor (SMT)
  • Tele-signaling unit (CLP) with potential-free contacts
  • Digital or analog voltmeters and ammeters for measuring battery voltage/current, and output voltage/current of the two output
  • 9 VRLA battery packs with capacity up to 200Ah, fixed in 3 shelves with liquid drain to retention basin (other solutions available)
  • Output voltage variation according to the temperature
  • Manual Battery Capacity Testing
  • Flexibility with various types of batteries
  • Warranty of 2 to 5 Years
  • EU Declaration of Conformity

3 | 2xAS24V6K+BAT | Dual Simplified DC Power Supply System plus Battery in the same cabinet

  • Input: Biphasic 400Vac / 50Hz / CFP > 0.99
  • 6kVA Isolation Transformer
  • Output at 24Vdc / 200A (2xFR4K24V100A) or 110Vdc / 50A (2xFR4K120V25A) or 48Vdc / 120A (2xFR4K48V60A)
  • Flexible modular configuration (N+1)
  • Hot Plugging Switching Rectifier (FR)
  • Diode reduction system (optional)
  • Hot plugging ground fault detection unit (DPT)
  • Independent 110Vdc Maximum Voltage Sensor (SMT)
  • Tele-signaling unit (CLP) with potential-free contacts
  • Digital or analog voltmeters and ammeters for measuring battery voltage/current and output voltage/current
  • VRLA type batteries with capacity up to 800Ah (24V) fixed in 2 shelves with liquid drainage to the retention basin (other solutions available)
  • Output voltage variation according to the temperature
  • Manual Battery Capacity Testing
  • Flexibility for various types of batteries
  • Warranty of 2 to 5 Years
  • EU Declaration of Conformity

4 | SCI110V-48V-230 | Wall DC/DC converters and DC/AC inverters system with two output voltage

  • Wall-mounted cabinet with a glass door and a second door to access the rear of DC/DC converters and DC/AC inverters, clamping terminals and other system components
  • NR1 DC Input Voltage: 250V/125V/110V/48V
  • NR2 DC Input Voltage: 250V/125V/110V/48V
  • Output Voltage at 48Vdc/66A (3 x SD type converters)
  • Other Output DC voltage possible 24Vdc/125A
  • By-Pass Input Voltage: 230Vac
  • Automatic bypass without micro-cuts / Manual bypass
  • Output Voltage at 230VAC/40A (4 x Bravo 25 type inverters)
  • Flexible modular configuration (N+1)
  • Voltage pluggable DC/DC (SD) converter
  • Voltage-pluggable DC/AC inverter (Bravo 25)
  • Interconnection with the RM (Fisocrom) Power Supply System via easy-to-fit Harting connector and Fisocrom supply
  • Information sent to the MSC’s of the RM type power supply systems includes: Information on the output voltages and currents of the DC/DC Converters and DC/AC Inverters
  • On the MSC of the system (RM) it is possible to access the resident Webserver Software (HTML5) and use TCP/IP Communications, IEC61850, IEC60870-5-104, as well as use a 10″ touch screen console (HMI) to view the menus with the information of this system
  • General Input Protection Circuit Breakers and DC/DC Converters and DC/DC Inverters Protection Circuit Breakers
  • Three 48Vdc outputs protected by Circuit Breaker (other options)
  • Six 230Vac outputs protected by Circuit Breaker (other options)
  • Potential-free contact tele-signaling (CLP)
  • Digital voltmeter and ammeter for measuring 48Vdc and 230Vac output voltage and current
  • 2 to 5 Year Warranty
  • EU Declaration of Conformity

5 | SD3000MW | Wall DC/DC converter system for one output voltage

  • Wall cabinet with a glass door and a second door to access the rear part of the Converters, clamping terminals and other system components
  • Input Voltage: 250Vdc / 125Vdc / 110Vdc / 48Vdc
  • Output Voltage at 24Vdc / 125A (3x SD type CC/CC converters)
  • Other possible output voltage 48Vdc / 66A
  • Flexible modular configuration (N+1)
  • Hot Plugging Switching Converter (SD)
  • General input protection circuit breaker and input and output protection circuit breakers for each DC/DC converter
  • Two Outputs available and protected by Circuit Breaker (other options available)
  • Tele-signaling unit (CLP) with potential-free contacts
  • Digital voltmeter and ammeter for measuring output voltage and current
  • Warranty of 2 to 5 Years
  • EU Declaration of Conformity

6 | SW110V12A | AC/DC system in wall cabinet with batteries included  

  • Polyester wall cabinet with a glass door and dimensions of 100cm(H) x 50cm(W) x 33cm(D)
  • Input: 100Vac to 264Vac / 50Hz / CFP > 0.99
  • Output: 110Vdc (AE1500-120 Rectifier Module) in parallel with 9 blocks (connected in series) of 7Ah/10h VRLA acid battery
  • Other options:
    • Output: 48Vdc (AE1500-48 Rectifier Module) in parallel with 4 blocks (connected in series) of 28Ah/10h VRLA acid battery
    • Output: 24Vdc (AE1500-24 Rectifier Module) in parallel with 2 blocks (connected in series) of 100Ah/10h VRLA battery
  • Variation of Output voltage depending on the cabinet’s interior temperature, controlled by the C22-URR unit
  • Battery current limiting controlled by I22-URR unit
  • Manual battery capacity test (unit C22-URR)
  • Stainless steel support and liquid retention basin
  • Input, Output and Battery Protection Circuit Breakers
  • Tele-signaling (CLP) by potentially potential-free contacts of General Fault / Mains Fault / Battery Fault / Low DC Voltage
  • Digital or analog voltmeters and ammeters for measuring output voltage, rectifier current, charging and discharging current of batteries
  • 2 Year Warranty
  • EU Declaration of Conformity