Skip to content

6 | SAR2xRM+2FC+2QDCC | Example of a Special Project in service since 2012 at the Belo Jardim Power Plant on Terceira Island (Azores)

  • 2 Rectifiers Cabinets of 110Vdc
  • 2 Converters DC/DC Cabinets of 24Vdc
  • 1 Distribution Cabinet of 110Vdc
  • 1 Distribution Cabinet of 24Vdc
  • Input: 400Vac/230Vac-50Hz/CFP > 0.99
  • Output at 110Vdc / 480A internal bus (12xFR6K-120Vdc/40A)
  • Output at 24Vdc / 540A internal bus (FC type DC/DC Converters)
FOR MAXIMUM CAPACITY IN OTHER SPECIAL PROJECTS:
  • 6 Rectifiers Cabinets of 110Vdc
  • 4 Converters DC/DC Cabinets of 48Vdc or 24Vdc
  • 2 Distribution Cabinet of 110Vdc
  • 2 Distribution Cabinet of 48Vdc or 24Vdc
  • Input: 400Vac/230Vac-50Hz/CFP > 0.99
  • Output at 110Vdc / 1500A internal bus (36xFR6K-120Vdc/40A)
  • Output at 48Vdc or 24Vdc up to 2000A internal bus (SD type DC/DC Converters)
  • Hot Plugging FR Switching rectifier and DC/DC converters (FC and SD)
  • Hot Plugging ground fault detection unit (DPT)
  • Independent 110Vdc Maximum Voltage Sensor (SMT)
  • 10″ touch color screen HMI webserver mirror
  • Hot Plugging (MSC) Supervision and Control Module
  • MSC Software Webserver resident (HTML5)
  • Communications TCP/IP / IEC61850 / IEC60870-5-104 / other
  • Emergency mode, in case of failure or extraction of the MSC, the Output voltages remain at the predefined values
  • Flexibility for various types of batteries
  • Battery Status and Charge Management
  • Warranty of 2 to 5 Years
  • EU Declaration of Conformity