- Two Rectifiers range RM250V36K, RM110V36K or RM48V36K
- Two Rectifiers range RM250V24K, RM110V24K or RM48V24K
- Input: 400Vac / 50Hz / CFP > 0.99
- Output Power up to 72kW (36kW + 36kW) – RM..36K
- Output Power up to 48kW (24kW + 24kW) – RM..24K
- Modular design (N+1) for flexible configuration
- Rectifier Switching Modules range FR6K250V/120V/48V – RM..36K
- Rectifier Switching Modules range FR4K250V/120V/48V – RM..24K
- Hot plugging Switching Rectifier Modules
- Hot plugging ground fault detection unit (DPT)
- Independent DC maximum voltage sensors (SMT)
- 10″ touch color screen HMI webserver mirror
- Hot plugging supervision and control module (MSC)
- Resident Webserver software (HTML5) on MSC
- Communications TCP/IP / IEC61850 / IEC60870-5-104 / others
- Emergency mode, in the event of failure or extraction of the MSC, the output DC voltage values remain at predefined values
- Flexibility for various types of batteries
- Battery Status and Charge Management
- Warranty of 2 to 5 Years
- EU Declaration of Conformity
2 | 2xRM110V36K9SD | Redundant system with two high power DC output voltage
- Two Rectifiers range RM250V36K, RM110V36K or RM48V36K + 9SD
- Input: 400Vac / 50Hz / PFC > 0.99
- Output at 110Vdc/480A (6+6xFR6K-120Vdc/40A)
- Output at 48Vdc/200A (9xSD DC/DC-48Vdc/22A Converters)
- Modular design (N+1) for flexible configuration
- Hot plugging Switching rectifier FR120V/40A
- Hot plugging SD DC/DC Converters
- Hot plugging ground fault detection unit (DPT)
- Independent maximum voltage sensor 110Vdc (SMT)
- 10″ touch color screen HMI webserver mirror
- Hot plugging supervision and control module (MSC)
- WebServer Software (HTML5) residing inside MSC
- Communications TCP/IP / IEC61850 / IEC60870-5-104 / others
- Emergency mode, in case of MSC failure or extraction, the 110Vdc and the 48Vdc, remain at the predefined values
- Flexibility for various types of batteries
- Battery Status and Charge Management
- Warranty of 2 to 5 Years
- EU Declaration of Conformity
3 | 2XRM110V18K / 2XRM110V12K | Redundant system with DC output
- Two Rectifiers range RM250V18K, RM110V18K or RM48V18K
- Two Rectifiers range RM250V12K, RM110V12K or RM48V12K
- Input: 400Vac / 50Hz / CFP > 0.99
- Output Power up to 36kW (18kW+18kW) – RM..18K
- Output Power up to 24kW (12kW+12kW) – RM..12K
- Modular design (N+1) for flexible configuration
- Rectifier Switching Modules range FR6K250V/120V/or 48V – RM..18K
- Rectifier Switching Modules range FR4K250V/120V/or 48V – RM..12K
- Hot plugging Switching Rectifier Modules
- Hot plugging ground fault detection unit (DPT)
- Independent DC maximum voltage sensors (SMT)
- 10″ touch color screen HMI webserver mirror
- Hot plugging supervision and control module (MSC)
- Resident Webserver software (HTML5) on MSC
- Communications TCP/IP / IEC61850 / IEC60870-5-104 / others
- Emergency mode, in the event of failure or extraction of the MSC, the output DC voltage values remain at predefined values
- Flexibility with various types of batteries
- Battery Status and Charge Management
- Warranty of 2 to 5 Years
- EU Declaration of Conformity
4 | AE48V9K3SD+BAT | System with output voltages of 48Vdc and 12Vdc plus 48V Battery in the same Cabinet
- Input: 400Vac / 50Hz / PFC > 0.99
- Isolation power input transformer 12kVA
- 48Vdc output (3XAE1500-90A in total)
- 12Vdc output (3xSD500-120A no total)
- Modular design (N+1) for flexible configuration
- Hot plugging Switching rectifier (AE1500)
- Hot plugging DC/DC Converters (SD500)
- Hot plugging ground fault detection unit (DPT)
- 10″ touch color screen HMI webserver mirror
- Hot plugging supervision and control module (MSC)
- WebServer Software (HTML5) residing inside MSC
- Communications TCP/IP / IEC61850 / IEC60870-5-104 / others
- Emergency mode, in case of failure or extraction of the MSC, the Voltage of 48Vdc and 12Vcc remains at the predefined values
- Two fixed shelves with liquid drainage for lower retention basin with capacity to receive two sets of 48V 200Ah (400Ah in total) VRLA type batteries with front terminals (other solutions available)
- Battery Status and Charge Management
- Warranty of 2 to 5 Years
- EU Declaration of Conformity
5 | SD3000 | Natural convection wall DC/DC converter system
- Wall cabinet with a glass door and a second door to access the rear part of the Converters, clamping terminals and other system components
- Input Voltage: 250Vdc/125Vdc/110Vdc/48Vdc
- Output Voltage at 24Vdc/90A (3x FC range CC/CC converters)
- Other possible output voltage 48Vdc/45A
- Flexible modular configuration (N+1)
- Hot Plugging Switching Converter (SD)
- These DC/DC converters (FC) have natural convection, and there are FC converters in continuous service that are over 30 years old, thus proving their reliability and durability.
- General input protection circuit breaker and input and output protection circuit breakers for each DC/DC converter
- Two Outputs available and protected by Circuit Breaker (other options available)
- Tele-signaling unit (CLP) with potential-free contacts
- Digital voltmeter and ammeter for measuring output voltage and current
- Warranty of 2 to 5 Years
- EU Declaration of Conformity
6 | FB110V12K230V | DC/AC Inverter System in wall cabinet
- Wall cabinet with a glass door and a second door to access the rear part of the Inverters, clamping terminals and other system components
- DC Input Voltage: 110Vdc (other voltage range available)
- 230Vac/50Hz bypass input
- Output 230Vac/50Hz/10kW/12kVa (4x Bravo 25 inverters)
- Flexible modular configuration (N+1)
- Hot Plugging Bravo 25 Inverters
- Protection circuit breakers for system inputs and outputs
- Two Outputs available and protected by Circuit Breaker (other options available)
- Emergency socket protected by circuit breakers with easy access
- Tele-signaling with potential-free contacts
- Digital voltmeters for measuring DC input voltage and AC output voltage
- Warranty of 2 Years
- EU Declaration of Conformity